Cookies

With your consent we use Google Analytics to see which pages are useful. Without it, the site works just the same. You can withdraw it any time in the footer. More in the privacy policy

Request a quote

Current ratings

Cross-sections, DC and AC current and contact dimensions from the IZAR 2024 catalogue, in one place.

Show connection type

Calculation conditions
  • approximate values
  • vertical mounting inside a building (no forced air flow)
  • max. air temperature 40 °C
  • operating temperature of the connector 90 °C
  • conductivity above 101% IACS
  • direct current (DC)

They apply to the PG, PE and SM tables. The PAL table is based on 70 °C and 57% IACS; the SE table gives the current at a temperature rise ΔT.

PG

Copper braided flexible connectors

Table of copper braided flexible connectors
No.Cross-section Q [mm²]DC current [A]AC current [A]Contact width B [mm]Contact length A [mm]Thickness S (approx.) [mm]
B = 20 mm
PG 202518117020203.5
PG 215026725120205
PG 227534232120206.5
PG 2310039937520207.5
B = 25 mm
PG 253021620325253.5
PG 266031329425255
PG 279039336925256
PG 2812046443625257.5
PG 2915053149925259
B = 30 mm
PG 305029928130304
PG 317537134930305
PG 3210043540930306
PG 3315055151830308
PG 3420065661730309.5
PG 35300756711303013.5
B = 40 mm
PG 407039437040404.5
PG 4114057253840406.5
PG 4221072368040408.5
PG 43280855804404011.5
PG 44350978919404013.5
PG 454201,0961,030404015.5
B = 50 mm
PG 5014061758050507
PG 5121077272650508.5
PG 52280910855505010
PG 533501,038976505012
PG 544201,1581,089505014
B = 60 mm
PG 6012060256660606
PG 6124087181960608.5
PG 623601,0891,024606010.5
PG 634801,2841,207606014.5
PG 646001,4641,376606017
B = 80 mm
PG 802801,03897680809.5
PG 814201,2891,212808011.5
PG 825601,5091,418808013.5
PG 837001,7101,607808016
PG 848401,8981,784808018
B = 100 mm
PG 1004801,4961,40610010011.5
PG 1017201,8611,74910010014.5
PG 1029602,1822,05110010018
PG 1031,2002,4752,32710010021
PG 1041,4402,7502,58510010024
PG 1051,6803,0122,83110010027
B = 120 mm
PG 1207201,9891,87012012013.5
PG 1219602,3222,18312012016
PG 1221,2002,6242,46712012019
PG 1231,4402,9052,73112012021.5
PG 1241,6803,1702,98012012027
PG 1251,9203,4013,19712012030
B = 140 mm
PG 1401,4403,040no data14014022.5
PG 1411,8003,461no data14014026
PG 1422,1603,825no data14014030
PG 1432,5204,204no data14014034
PG 1442,8804,532no data14014038
PG 1452,8804,532no data14014038
B = 150 mm
PG 1501,0802,6572,49815015017
PG 1511,4403,1052,91915015021
PG 1521,8003,5003,29015015024
PG 1532,1603,8903,65715015029
PG 1542,5204,2373,98315015032
PG 1552,8804,5794,30415015036
B = 160 mm
PG 1601,4403,1762,98516016021
PG 1611,8003,5863,37116016024.5
PG 1622,1603,9653,72716016028
PG 1632,5204,3174,05816016031
PG 1642,8804,6514,37216016034
B = 180 mm
PG 1801,4403,3063,10818018020
PG 1811,8003,7233,50018018023
PG 1822,1604,1093,86218018026
PG 1832,5204,4704,20218018029
PG 1842,8804,8134,52418018032
B = 200 mm
PG 2001,4403,4283,22220020019
PG 2011,9203,9863,74720020022.5
PG 2022,4004,4964,22620020026
PG 2032,8804,9694,67120020030
PG 2043,3605,4025,07820020033
B = 220 mm
PG 2201,4403,5453,33222022018
PG 2211,9204,1283,88022022022
PG 2222,4004,6444,36522022025
PG 2232,8805,1184,81122022028
PG 2243,3605,5625,22822022031
  • Approximate values calculated according to the following parameters:
  • Mounting vertically inside a building (no forced air flow), DC.
  • Max. air temperature 40 °C.
  • Operating temperature of the connector 90 °C.
  • Conductivity above 101% IACS.
  • PG 140–145: AC current to be confirmed (in the 2024 catalogue the AC column in this group is shifted by one row, and PG 145 repeats PG 144).

Source: IZAR catalogue 2024, p. 5

PE

Flexible press-welded copper connectors

Table of flexible press-welded copper connectors
No.Cross-section Q [mm²]DC current [A]AC current [A]Contact width B [mm]Contact length A [mm]Thickness S (approx.) [mm]
B = 20 mm
PE 2010037735420205
PE 21200584549202010
PE 22300773727202015
PE 23400954897202020
B = 40 mm
PE 4020066962840405
PE 41400997937404010
PE 426001,2811,204404015
PE 438001,5451,452404020
B = 50 mm
PE 5025081076150505
PE 515001,1961,124505010
PE 527501,5251,434505015
PE 531,0001,8271,717505020
B = 60 mm
PE 6030094889160605
PE 616001,3921,308606010
PE 629001,7641,658606015
PE 631,2002,1041,978606020
B = 80 mm
PE 804001,2201,14780805
PE 818001,7751,669808010
PE 821,2002,2332,099808015
PE 831,6002,6462,487808020
B = 100 mm
PE 1005001,4851,3961001005
PE 1011,0002,1502,02110010010
PE 1021,5002,6932,53110010015
PE 1032,0003,1762,98510010020
B = 120 mm
PE 1206001,7471,6421201205
PE 1211,2002,5202,36912012010
PE 1221,8003,1452,95612012015
PE 1232,4003,6983,47612012020
B = 140 mm
PE 1407002,0051,8851401405
PE 1411,4002,8842,71114014010
PE 1422,1003,5913,37614014015
PE 1432,8004,2133,96014014020
B = 160 mm
PE 1608002,2612,1251601605
PE 1611,6003,2453,05016016010
PE 1622,4004,0323,79016016015
PE 1633,2004,7224,43916016020
  • Approximate values calculated according to the following parameters:
  • Mounting vertically inside a building (no forced air flow), DC.
  • Max. air temperature 40 °C.
  • Operating temperature of the connector 90 °C.
  • Conductivity above 101% IACS.

Source: IZAR catalogue 2024, p. 6

PAL

Aluminium flexible connectors

PAL aluminium flexible connectors: cross-section, DC current and contact-area dimensions (B, A, S)
No.Cross-section [mm²]DC current [A]B [mm]A [mm]S (approx.) [mm]
B = 40 mm
PAL 4520037640405
PAL 410400560404010
PAL 415675720404015
B = 50 mm
PAL 5525045450505
PAL 510500671505010
PAL 515750855505015
B = 60 mm
PAL 6530053160605
PAL 610600779606010
PAL 615900988606015
B = 80 mm
PAL 8540068180805
PAL 810800992808010
PAL 8151,2001,248808015
B = 100 mm
PAL 1055008281001005
PAL 1101,0001,19910010010
PAL 1151,5001,50210010015
B = 120 mm
PAL 1256009731201205
PAL 12101,2001,40312012010
PAL 12151,8001,75112012015
B = 140 mm
PAL 145no data1,1151401405
PAL 1410no data1,60414014010
PAL 1415no data1,99714014015
B = 200 mm
PAL 205no data1,5322002005
PAL 2010no data2,19320020010
PAL 2015no data2,71720020015
  • Approximate values calculated according to the following parameters:
  • Mounting vertically inside a building (no forced air flow), DC.
  • Max. air temperature 40 °C.
  • Operating temperature of the connector 70 °C.
  • Conductivity above 57% IACS.
  • Notes on the 2024 catalogue print: the conditions (70 °C, 57% IACS), PAL 55 (DC 454 A, B 50 mm) and the dimensions of PAL 205, 2010 and 2015 (B = A = 200 mm, S 5, 10 and 15 mm) are taken from the previous IZAR table because of print errors in the catalogue. Cross-sections marked “–” are to be confirmed.

Source: IZAR catalogue 2024, p. 8

SE

Flexible busbars

SE flexible busbars: cross-section, contact-area dimensions and DC current at a temperature rise ΔT of 70, 50 and 30 °C
No.Cross-section [mm²]Contact area B × S × K [mm]DC current at ΔT 70 °C [A]DC current at ΔT 50 °C [A]DC current at ΔT 30 °C [A]
B = 20 mm
SE 2004020 × 2 × 1327274215
SE 2016020 × 3 × 1427361281
SE 2028020 × 4 × 1476401314
SE 20310020 × 5 × 1498421327
SE 20412020 × 6 × 1546463358
SE 20518020 × 9 × 1647549416
SE 20620020 × 10 × 1762645502
B = 24 mm
SE 2404824 × 2 × 1450380295
SE 2417224 × 3 × 1493413320
SE 2429624 × 4 × 1551465361
SE 24312224 × 5 × 1610514398
SE 24414324 × 6 × 1671566438
SE 24519224 × 8 × 1802678525
SE 24621824 × 9 × 1869735no data
SE 24724324 × 10 × 1948803592
B = 32 mm
SE 3206432 × 2 × 1481406315
SE 3219632 × 3 × 1571483372
SE 32212832 × 4 × 1648548425
SE 32316232 × 5 × 1758642496
SE 32419232 × 6 × 1846715555
SE 32525632 × 8 × 11,018863667
SE 32628832 × 9 × 11,126952736
SE 32732232 × 10 × 11,2321,041805
B = 40 mm
SE 4008040 × 2 × 1538455352
SE 40112140 × 3 × 1617522405
SE 40216340 × 4 × 1727615476
SE 40320340 × 5 × 1902761593
SE 40424040 × 6 × 11,018860667
SE 40532040 × 8 × 11,2331,041805
SE 40636040 × 9 × 11,3291,123872
SE 40740240 × 10 × 11,4031,182915
B = 50 mm
SE 50015250 × 3 × 1701592462
SE 50120150 × 4 × 1862727563
SE 50225250 × 5 × 11,102932718
SE 50330150 × 6 × 11,2261,034802
SE 50440150 × 8 × 11,3931,175912
SE 50545050 × 9 × 11,5231,284997
SE 50650450 × 10 × 11,6541,3931,082
B = 63 mm
SE 63018963 × 3 × 1798675522
SE 63125263 × 4 × 11,012855661
SE 63231563 × 5 × 11,2211,032797
SE 63337863 × 6 × 11,4391,217941
SE 63450463 × 8 × 11,6521,3961,085
SE 63556763 × 9 × 11,7721,4981,162
SE 63663163 × 10 × 11,8951,6021,242
B = 80 mm
SE 80024280 × 3 × 1983827641
SE 80132480 × 4 × 11,2031,015785
SE 80240380 × 5 × 11,3921,175910
SE 80348080 × 6 × 11,6261,3741,065
SE 80464280 × 8 × 11,8951,6031,244
SE 80572280 × 9 × 11,9981,6891,311
SE 80680080 × 10 × 12,1051,7741,377
B = 100 mm
SE 1000401100 × 4 × 11,4461,225947
SE 1001501100 × 5 × 11,6351,3851,075
SE 1002601100 × 6 × 11,8431,5511,205
SE 1003800100 × 8 × 12,1471,8151,404
SE 1004900100 × 9 × 12,2521,9041,473
SE 10051,002100 × 10 × 12,3521,9851,535
SE 10061,100100 × 11 × 12,4302,0531,588
SE 10071,200100 × 12 × 12,5032,1151,636
B = 120 mm
SE 12001,200120 × 10 × 12,7552,3321,794
  • Approximate values calculated according to the following parameters:
  • Mounting vertically inside a building (no forced air flow), DC.
  • Max. air temperature 40 °C.
  • Conductivity above 101% IACS.
  • The current is given for a busbar temperature rise ΔT; the condition “connector operating temperature 90 °C” printed in the catalogue is to be confirmed.
  • SE 246, ΔT 30 °C: value to be confirmed (the catalogue prints 917 A, more than at ΔT 50 °C).

Source: IZAR catalogue 2024, p. 11

SM

Copper busbars

Table of copper busbars
No.Cross-section [mm²]DC current [A]Width B [mm]Thickness S [mm]
B = 30 mm
SM 305150525305
SM 3103007943010
SM 3154501,0313015
B = 40 mm
SM 405200670405
SM 4104009974010
SM 4156001,2814015
B = 50 mm
SM 505250810505
SM 5105001,1965010
SM 5157501,5255015
B = 60 mm
SM 605300948605
SM 6106001,3926010
SM 6159001,7646015
B = 80 mm
SM 8054001,220805
SM 8108001,7758010
SM 8151,2002,2338015
B = 100 mm
SM 10055001,4851005
SM 10101,0002,15010010
SM 10151,5002,69310015
B = 120 mm
SM 12056001,7471205
SM 12101,2002,52012010
SM 12151,8003,14512015
B = 160 mm
SM 16101,6003,24516010
SM 16152,4004,03216015
SM 16203,2004,72216020
  • Approximate values calculated according to the following parameters:
  • Mounting vertically inside a building (no forced air flow), DC.
  • Max. air temperature 40 °C.
  • Operating temperature of the connector 90 °C.
  • Conductivity above 101% IACS.

Source: IZAR catalogue 2024, p. 12

TP

Braided and rolled tapes, copper cords

Table of braided / stranded flexible cords
Nominal cross-section [mm²]Ø of wire [mm]Overall Ø, approx. [mm]
60.1/0.23.7
80.1/0.24.2
100.1/0.24.7
120.1/0.25.2
160.1/0.26
250.1/0.27.6
350.1/0.29
500.1/0.210.7
700.1/0.212.7
950.1/0.214.8
1200.1/0.218
1500.120
1850.121

Source: IZAR catalogue 2024, p. 15

Table of braided rolled tapes
Cross-section [mm²]Ø of wire [mm]Width ±20% [mm]Thickness ±20% [mm]Construction ±2% [n × n]Weight ±12% [kg/km]
100.1101.724 × 53100
10no data101.724 × 13100
170.218224 × 22/23170
250.1222.546 × 66250
250.2222.548 × 16250
350.1302.548 × 93350
350.2302.548 × 23350
500.1332.548 × 133500
500.2332.548 × 33500
700.1453.548 × 186700
700.2354.548 × 46/47700
950.150448 × 253950
950.250448 × 63950
1200.160448 × 3191,200
1500.165548 × 3991,500
  • Construction of 35 mm² / 0.20 mm and 50 mm² / 0.10 mm taken from the previous IZAR table (print error in the catalogue). Wire diameter in the second 10 mm² row to be confirmed.

Source: IZAR catalogue 2024, p. 15

Send an enquiry or a drawing

Tell us the product code, current and quantity, or send a drawing. Our sales team will prepare a quotation.

Sales

Maciej Połacik Sales Director

+48 887 137 777

maciej@izar.pl