Cookies

With your consent we use Google Analytics to see which pages are useful. Without it, the site works just the same. You can withdraw it any time in the footer. More in the privacy policy

Request a quote

SEFlexible connections

Flexible busbars

Copper strips in vinyl insulation that bend and twist at a very small radius.

Several flexible busbars in black insulation, bent into various shapes, with exposed copper ends with holes; markings printed on the insulation
Cross-section in the table
40–1,200 mm²
Width B in the table
20–120 mm
DC current, ΔT 30–70 °C
215–2,755 A
Length
2 m, 3 m to order
Insulation
vinyl compound

Design and options

SE flexible busbars are stacks of copper strips in vinyl-compound insulation that can be bent and twisted at a very small radius and connected without cable lugs.

Construction
many stacked copper strips
Cross-section vs. rating
40% smaller than other connections for the same current load
Connection
no cable lugs required
Custom design
custom bent and drilled connections to the customer’s design

Types

Shapes from the catalogue. Give the dimensions in your enquiry or on a drawing.

  • Type T

    90° twist

  • Type L

    L-bend

  • Type U

    U-bend

Catalogue drawings
Drawing of a flexible busbar in top and side view: length L, width B and dimensions S and K
Type T drawing: flexible busbar twisted through 90°
Type L drawing: flexible busbar with a right-angle bend, dimensions h and Ld
Type U drawing: flexible busbar bent into a U shape, dimensions h and Ld

Current rating table

Approximate values from the IZAR 2024 catalogue. The calculation conditions are below the table.

SE flexible busbars: cross-section, contact-area dimensions and DC current at a temperature rise ΔT of 70, 50 and 30 °C
No.Cross-section [mm²]Contact area B × S × K [mm]DC current at ΔT 70 °C [A]DC current at ΔT 50 °C [A]DC current at ΔT 30 °C [A]
B = 20 mm
SE 2004020 × 2 × 1327274215
SE 2016020 × 3 × 1427361281
SE 2028020 × 4 × 1476401314
SE 20310020 × 5 × 1498421327
SE 20412020 × 6 × 1546463358
SE 20518020 × 9 × 1647549416
SE 20620020 × 10 × 1762645502
B = 24 mm
SE 2404824 × 2 × 1450380295
SE 2417224 × 3 × 1493413320
SE 2429624 × 4 × 1551465361
SE 24312224 × 5 × 1610514398
SE 24414324 × 6 × 1671566438
SE 24519224 × 8 × 1802678525
SE 24621824 × 9 × 1869735no data
SE 24724324 × 10 × 1948803592
B = 32 mm
SE 3206432 × 2 × 1481406315
SE 3219632 × 3 × 1571483372
SE 32212832 × 4 × 1648548425
SE 32316232 × 5 × 1758642496
SE 32419232 × 6 × 1846715555
SE 32525632 × 8 × 11,018863667
SE 32628832 × 9 × 11,126952736
SE 32732232 × 10 × 11,2321,041805
B = 40 mm
SE 4008040 × 2 × 1538455352
SE 40112140 × 3 × 1617522405
SE 40216340 × 4 × 1727615476
SE 40320340 × 5 × 1902761593
SE 40424040 × 6 × 11,018860667
SE 40532040 × 8 × 11,2331,041805
SE 40636040 × 9 × 11,3291,123872
SE 40740240 × 10 × 11,4031,182915
B = 50 mm
SE 50015250 × 3 × 1701592462
SE 50120150 × 4 × 1862727563
SE 50225250 × 5 × 11,102932718
SE 50330150 × 6 × 11,2261,034802
SE 50440150 × 8 × 11,3931,175912
SE 50545050 × 9 × 11,5231,284997
SE 50650450 × 10 × 11,6541,3931,082
B = 63 mm
SE 63018963 × 3 × 1798675522
SE 63125263 × 4 × 11,012855661
SE 63231563 × 5 × 11,2211,032797
SE 63337863 × 6 × 11,4391,217941
SE 63450463 × 8 × 11,6521,3961,085
SE 63556763 × 9 × 11,7721,4981,162
SE 63663163 × 10 × 11,8951,6021,242
B = 80 mm
SE 80024280 × 3 × 1983827641
SE 80132480 × 4 × 11,2031,015785
SE 80240380 × 5 × 11,3921,175910
SE 80348080 × 6 × 11,6261,3741,065
SE 80464280 × 8 × 11,8951,6031,244
SE 80572280 × 9 × 11,9981,6891,311
SE 80680080 × 10 × 12,1051,7741,377
B = 100 mm
SE 1000401100 × 4 × 11,4461,225947
SE 1001501100 × 5 × 11,6351,3851,075
SE 1002601100 × 6 × 11,8431,5511,205
SE 1003800100 × 8 × 12,1471,8151,404
SE 1004900100 × 9 × 12,2521,9041,473
SE 10051,002100 × 10 × 12,3521,9851,535
SE 10061,100100 × 11 × 12,4302,0531,588
SE 10071,200100 × 12 × 12,5032,1151,636
B = 120 mm
SE 12001,200120 × 10 × 12,7552,3321,794
  • Approximate values calculated according to the following parameters:
  • Mounting vertically inside a building (no forced air flow), DC.
  • Max. air temperature 40 °C.
  • Conductivity above 101% IACS.
  • The current is given for a busbar temperature rise ΔT; the condition “connector operating temperature 90 °C” printed in the catalogue is to be confirmed.
  • SE 246, ΔT 30 °C: value to be confirmed (the catalogue prints 917 A, more than at ΔT 50 °C).

Source: IZAR catalogue 2024, p. 11

Where they are used

Industries in which this connection type is used.

According to the catalogue

  • switchgear cabinets and distribution boards

What to include in your enquiry

  1. size from the table (e.g. SE 400) or cross-section [mm²]
  2. 2 or 3 m lengths, or a finished part to your design
  3. bends (type T, L, U) and holes
  4. quantity

Have a drawing? Email it to maciej@izar.pl.

Request a quote

Questions about SE

Do flexible busbars need cable lugs?

No. SE busbars are connected without cable lugs, and even the largest ones can be bent, twisted and folded at a very small radius.

How much smaller is the cross-section of a flexible busbar?

By 40% compared with other connections for the same current load (IZAR catalogue data).

In which lengths are SE busbars supplied?

As standard in 2 m lengths, and 3 m to order. IZAR also makes finished parts from insulated busbars, bent and drilled to the customer’s design.

What does ΔT mean in the SE table?

The temperature rise of the busbar. The table gives the DC current for ΔT 70, 50 and 30 °C; for example, SE 400 (80 mm²) carries 538, 455 and 352 A respectively.

Send an enquiry or a drawing

Give us the code, current and quantity, or send a drawing. Our sales team will prepare a quotation.

Sales

Maciej Połacik Sales Director

+48 887 137 777

maciej@izar.pl